Custom Electronics Ltd AOV Multi-zone Control Unit Installation Document March 2008 Version 1a
4) PCB Connections Diag 1. Motherboard Layout Diag. 2 Zone Card Layout
5) Technical Specification Power Supply Unit 5 Amp / 10 Amp Input Supply 240v AC (+/- 10%) 50/60Hz Input Fuse 1 - 10 Zone 5Amp, 25mm UK Ty
6) Installation Instructions 1.1 Environment The units are suitable for use in most indoor environments where an IP rating of IP30 is acceptable. 1.2
7) Connection Guide 1.1 Actuator Connections Each actuator requires a 2 core cable wired direct to the control panel and each pair must be connected
8) Wiring Installation Upon installation maximum cable lengths must be adhered to, use the following table to calculate the maximum cable lengths, ta
Power 24V AOV Multi-zone Quick Guide Connection Sheet AOV Manual Control Point S E R I E S Multiple Triggering M N/CActuator and Triggering Con
Quick guide • Fix unit on to wall using mounting holes provided. • Remove cable ties securing zone cards. • Connect mains via lower power suppl
Jumper Settings For Zone 1 to operate as a master zone the following steps must be adhered to: 5 Zone Panel Step 1 The following jumpers should be
Table of Contents 1) General overview 2) System Schematics i. Standard auto system ii. Auto system with break glass units iii. Auto system with de
1) General Overview This control unit is for use with most Automatic Opening Vents and can be used with other equipment that requires forward/reverse
2) i Standard Auto System
2) ii Auto system with break glass units
2) iii Auto system with detectors
2) iv Auto system combination
2) v Manual Control System Combination
3) Internal Layout and Fixing Details A - Mains Input B – Power Supply (1 to 30 amp) C – AOV Main Board D – Indicator Connections to Front Panel E